Implementation of electrode boilers for frequency control of utility grids
Loading...
Date
Authors
Verra, Huibert Antonie
Journal Title
Journal ISSN
Volume Title
Publisher
Abstract
This thesis successfully demonstrates an algorithm for improving the power control of a high-voltage electrode boiler being utilized for load-frequency control, by actively adjusting the slopes of XY-curves used for boiler water level control set-point and outputs as a function of boiler temperature.
The increase in transient energy co-generation, such as wind-power, places greater demands on an electrical grid for maintaining load-frequency control. A common method for load-frequency control used in Europe is decentralized co-generation plants with high-voltage electrode boilers. These provide a secondary benefit of hot water district consumer use.
Current high-voltage electrode boilers used for load-frequency control do not account for water temperature when determining conductivity and water-level set-points. Set-point curves are determined at the time of commissioning and then set. This thesis develops and tests an algorithm that accounts for boiler water temperature and dynamically adjusts the XY-curves that define the system behavior. The tested algorithm showed a clear improvement in maintaining load-frequency control, reducing the mean power error to O ± 0.5%.
Description
M.S.--University of Oklahoma, 2014
Includes bibliographical references (leaves 64-66).
Includes bibliographical references (leaves 64-66).